Garnek pianowy

Title:

Description:

Garnek pianowy

Foam chambers are elements of fixed fire-extinguishing foam systems – for heavy foam. These systems are used for fire fighting in tanks with flammable media (I and II risk class). Foam chambers are used in tanks with solid roof. The task of foam chamber is to isolate foam system piping and the atmosphere against fumes of medium stored in the tank. Isolation provides a vapour seal – made of teflon foil or glass plate. After the system is turned on, the foam destroys the membrane and fills the tank. Foam chamber connects with installation using standard flanges according to PN EN 1092-1:2007

Do sklepu internetowego


Materiał:
– Płaszcz zbiornika: stal.
– Kołnierze: stal.
– Bezpiecznik: teflon lub szkło.
Ciśnienie pracy maksymalne – 0,55 MPa.
Ciśnienie rozerwania bezpiecznika –0,011 ÷ 0,025 MPa.
Wykończenie: cynkowanie ogniowe lub lakierowanie.
Wykonanie specjalne: ze stali kwasoodpornej.


Typ garnkaNumer katalogowyWymiar A
DN
Wymiar A
PN
Wymiar B
DN
Wymiar B
PN
Wymiar C
[mm]
Wymiar D
[mm]
Średnica E
[mm]
Wymiar H
[mm]
Waga
[kg]
GP 4000401200000080161251623026032452045
GP 8000401300000080161501622027532455549
GP 1200/160004014000000100162501629036040671096

NIP: 542-020-23-45

REGON: 000511433

KRS: 0000301100

Media społecznościowe