Garnek pianowy

Garnek pianowy

Garnek pianowy

Foam chambers are elements of fixed fire-extinguishing foam systems – for heavy foam. These systems are used for fire fighting in tanks with flammable media (I and II risk class). Foam chambers are used in tanks with solid roof. The task of foam chamber is to isolate foam system piping and the atmosphere against fumes of medium stored in the tank. Isolation provides a vapour seal – made of teflon foil or glass plate. After the system is turned on, the foam destroys the membrane and fills the tank. Foam chamber connects with installation using standard flanges according to PN EN 1092-1:2007

  • Materiał:
    - Płaszcz zbiornika: stal.
    - Kołnierze: stal.
    - Bezpiecznik: teflon lub szkło.
  • Ciśnienie pracy maksymalne – 0,55 MPa.
  • Ciśnienie rozerwania bezpiecznika –0,011 ÷ 0,025 MPa.
  • Wykończenie: cynkowanie ogniowe lub lakierowanie.
  • Wykonanie specjalne: ze stali kwasoodpornej.

Typ garnka Numer katalogowy Wymiar A
DN
Wymiar A
PN
Wymiar B
DN
Wymiar B
PN
Wymiar C
[mm]
Wymiar D
[mm]
Średnica E
[mm]
Wymiar H
[mm]
Waga
[kg]
GP 400 04012000000 80 16 125 16 230 260 324 520 45
GP 800 04013000000 80 16 150 16 220 275 324 555 49
GP 1200/1600 04014000000 100 16 250 16 290 360 406 710 96